Measure voltage … without test leads
Measure voltage up to 1000 V ac through the open fork, without test lead contact to live voltage.+ Without opening covers or removing wire nuts. On wires up to AWG 4/0 (120 mm2), carrying as much as 200 A. It will change your job. Safer. Faster. Easier.
Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.
Product Highlights
- FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage+
- Simultaneous voltage and current display – shows all power supply measurements at a glance for efficient trouble shooting
- 1 to 1000 V ac or dc (T6-1000)
- 0.1 to 200 A ac
- True-rms voltage and current
- Resistance 1 Ω to 100 kΩ
- Frequency measurement 45 Hz to 66 Hz
- Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
- HOLD button temporarily freezes the reading for easy viewing
- Easy to read display with backlight
- Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation
- Standard two-year warranty; extendable to 4 years through product registration within 45 days of purchase*
Measurement Specifications |
Function |
Requires test leads |
Range |
Resolution |
Accuracy[1] |
FieldSense
ac voltage True-rms |
No |
1000 V |
1 V |
± (3 % + 3 counts) 45 Hz – 66 Hz[2][3] |
FieldSense
ac current True-rms |
No |
200.0 A |
0.1 A |
± (3% + 3 counts) 45 Hz – 66 Hz |
FieldSense
frequency (Hz) |
No |
45 Hz – 66 Hz |
1 Hz |
± (1% + 2 counts)[3] |
Volts ac True-rms |
Yes |
1000 V |
1 V |
± (1.5% + 2 counts) 45 Hz – 66 Hz |
Volts dc |
Yes |
1000 V |
1 V |
± (1% + 2 counts) |
Resistance |
Yes |
2000 Ω |
1 Ω |
± (1% + 2 counts) |
Yes |
20.00 kΩ |
0.01 kΩ |
Yes |
100.0 kΩ |
0.1 kΩ |
Safety |
|
1000 V CAT III
600 V CAT IV |
|
|
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.
Accuracy[3]: FieldSense is specified from 16 V to 100 % of range. |
General Specifications |
Calibration |
1-year calibration cycle |
Dimensions |
61.1 x 259.3 x 43.8 mm |
Jaw opening |
17.8 mm |
Weight |
0.35 kg (0.78 lb) |
Temperature
Operating:
Storage: |
-10 °C to +50 °C (14 °F to 122 °F)
-30 °C to +60 °C (-22 °F to +140 °F) |
Altitude
Operating:
Storage: |
2,000 m (6,562 feet)
10,000 m (32,808 feet) |
Relative Humidity |
0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F) |
Battery Type and Life |
2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense |
Temperature coefficient |
0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F) |
Safety |
IEC/EN 61010-1: Pollution Degree 2 |
Electromagnetic Environment |
IEC/EN 61326-1: Portable |
|
|
|
|
|
|
|