OVERVIEW & SPECIFICATION
The Fluke 434 II Energy Analyzer is the ideal tool for energy logging. Utilizing the new Energy Loss Calculator function, the 434 II measures the fiscal cost of energy wasted due to poor power quality. This energy monetization capability allows you to identify the most energy-wasteful areas of your facility so you can determine potential energy saving solutions. Add basic power quality measurements to the package and you’re got yourself one powerful troubleshooting tool.
Model | Measurement range | Resolution | Accuracy | |
Volt | ||||
Vrms (ac+dc) | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 0.5% of nominal voltage**** |
Vpk | 1 Vpk to 1400 Vpk | 1 V | 5% of nominal voltage | |
Voltage Crest Factor (CF) | 1.0 > 2.8 | 0.01 | ± 5 % | |
Vrms½ | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 1% of nominal voltage |
Vfund | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 0.5% of nominal voltage |
Amps (accuracy excluding clamp accuracy) | ||||
Amps (ac +dc) | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Apk | i430-Flex | 8400 Apk | 1 Arms | ± 5 % |
1mV/A | 5500 Apk | 1 Arms | ± 5 % | |
A Crest Factor (CF) | 1 to 10 | 0.01 | ± 5 % | |
Amps½ | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 1% ± 10 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 1% ± 10 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 1% ± 10 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 1% ± 10 counts | |
Afund | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Hz | ||||
Hz | Fluke 434 @ 50 Hz nominal | 42.50 Hz to 57.50 Hz | 0.01 Hz | ± 0.01 Hz |
Fluke 434 @ 60 Hz nominal | 51.00 Hz to 69.00 Hz | 0.01 Hz | ± 0.01 Hz | |
Power | ||||
Watts (VA, var) | i430-Flex | max 6000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts |
1 mV/A | max 2000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts | |
Power factor (Cos j/DPF) | 0 to 1 | 0.001 | ± 0.1% @ nominal load conditions | |
Energy | ||||
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts | |
Energy loss | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts Excluding line resistance accuracy | |
Harmonics | ||||
Harmonic order (n) | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 | |||
Inter-harmonic order (n) | OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 | |||
Volts | %f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1 % |
%r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 1000 V | 0.1 V | ± 5% * | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Amps | %f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1% |
%r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 600 A | 0.1 A | ± 5% ± 5 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Watts | %f or %r | 0.0 % to 100 % | 0.1 % | ± n x 2% |
Absolute | Depends on clamp scaling and V nominal | — | ± 5% ± n x 2 % ± 10 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 5 % | |
Phase Angle | -360° to +0° | 1° | ± n x 1° | |
Flicker | ||||
Plt, Pst, Pst(1min) Pinst | 0.00 to 20.00 | 0.01 | ± 5 % | |
Unbalance | ||||
Volts | % | 0.0 % to 20.0 % | 0.1 % | ± 0.1 % |
Amps | % | 0.0 % to 20.0 % | 0.1% | ± 1 % |
Mains signaling | ||||
Threshold levels | Threshold, limits and signaling duration is programable for two signaling frequencies | — | — | |
Signaling frequency | 60 Hz to 3000 Hz | 0.1 Hz | ||
Relative V% | 0 % to 100 % | 0.10 % | ± 0.4 % | |
Absolute V3s (3 second avg.) | 0.0 V to 1000 V | 0.1 V | ± 5 % of nominal voltage |
General specifications |
|
Case | Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
Display | Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated |
Memory | 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) |
Real-time clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Environmental |
|
Operating temperature | 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery |
Storage temperature | -20 °C ~ +60 °C |
Humidity | +10 °C ~ +30 °C: 95% RH non-condensing +30 °C ~ +40 °C: 75% RH non-condensing +40 °C ~ +50 °C: 45% RH non-condensing |
Maximum operating altitude | Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V Maximum storage altitude 12 km (40,000 ft) |
Electro-Magnetic-Compatibility (EMC) | EN 61326 (2005-12) for emission and immunity |
Interfaces | mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery |
Warranty | Three years (parts and labor) on main instrument, one year on accessories |
Fluke 434
OVERVIEW & SPECIFICATION
The Fluke 434 II Energy Analyzer is the ideal tool for energy logging. Utilizing the new Energy Loss Calculator function, the 434 II measures the fiscal cost of energy wasted due to poor power quality. This energy monetization capability allows you to identify the most energy-wasteful areas of your facility so you can determine potential energy saving solutions. Add basic power quality measurements to the package and you’re got yourself one powerful troubleshooting tool.
Model | Measurement range | Resolution | Accuracy | |
Volt | ||||
Vrms (ac+dc) | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 0.5% of nominal voltage**** |
Vpk | 1 Vpk to 1400 Vpk | 1 V | 5% of nominal voltage | |
Voltage Crest Factor (CF) | 1.0 > 2.8 | 0.01 | ± 5 % | |
Vrms½ | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 1% of nominal voltage |
Vfund | 434-II | 1 V to 1000 V phase to neutral | 0.1 V | ± 0.5% of nominal voltage |
Amps (accuracy excluding clamp accuracy) | ||||
Amps (ac +dc) | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Apk | i430-Flex | 8400 Apk | 1 Arms | ± 5 % |
1mV/A | 5500 Apk | 1 Arms | ± 5 % | |
A Crest Factor (CF) | 1 to 10 | 0.01 | ± 5 % | |
Amps½ | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 1% ± 10 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 1% ± 10 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 1% ± 10 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 1% ± 10 counts | |
Afund | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Hz | ||||
Hz | Fluke 434 @ 50 Hz nominal | 42.50 Hz to 57.50 Hz | 0.01 Hz | ± 0.01 Hz |
Fluke 434 @ 60 Hz nominal | 51.00 Hz to 69.00 Hz | 0.01 Hz | ± 0.01 Hz | |
Power | ||||
Watts (VA, var) | i430-Flex | max 6000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts |
1 mV/A | max 2000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts | |
Power factor (Cos j/DPF) | 0 to 1 | 0.001 | ± 0.1% @ nominal load conditions | |
Energy | ||||
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts | |
Energy loss | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts Excluding line resistance accuracy | |
Harmonics | ||||
Harmonic order (n) | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 | |||
Inter-harmonic order (n) | OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 | |||
Volts | %f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1 % |
%r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 1000 V | 0.1 V | ± 5% * | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Amps | %f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1% |
%r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 600 A | 0.1 A | ± 5% ± 5 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Watts | %f or %r | 0.0 % to 100 % | 0.1 % | ± n x 2% |
Absolute | Depends on clamp scaling and V nominal | — | ± 5% ± n x 2 % ± 10 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 5 % | |
Phase Angle | -360° to +0° | 1° | ± n x 1° | |
Flicker | ||||
Plt, Pst, Pst(1min) Pinst | 0.00 to 20.00 | 0.01 | ± 5 % | |
Unbalance | ||||
Volts | % | 0.0 % to 20.0 % | 0.1 % | ± 0.1 % |
Amps | % | 0.0 % to 20.0 % | 0.1% | ± 1 % |
Mains signaling | ||||
Threshold levels | Threshold, limits and signaling duration is programable for two signaling frequencies | — | — | |
Signaling frequency | 60 Hz to 3000 Hz | 0.1 Hz | ||
Relative V% | 0 % to 100 % | 0.10 % | ± 0.4 % | |
Absolute V3s (3 second avg.) | 0.0 V to 1000 V | 0.1 V | ± 5 % of nominal voltage |
General specifications |
|
Case | Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
Display | Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated |
Memory | 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) |
Real-time clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Environmental |
|
Operating temperature | 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery |
Storage temperature | -20 °C ~ +60 °C |
Humidity | +10 °C ~ +30 °C: 95% RH non-condensing +30 °C ~ +40 °C: 75% RH non-condensing +40 °C ~ +50 °C: 45% RH non-condensing |
Maximum operating altitude | Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V Maximum storage altitude 12 km (40,000 ft) |
Electro-Magnetic-Compatibility (EMC) | EN 61326 (2005-12) for emission and immunity |
Interfaces | mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery |
Warranty | Three years (parts and labor) on main instrument, one year on accessories |